An 8.5 or 9.5kw shower requires 10mm2 twin and earth cable if the cable run to the consumer unit is more than 15 metres. 8.5kw showers can use 6mm2 cable on runs less than 15m. The shower must be permanently connected to the electricity supply via a double pole isolating switch. A suitably sized MCB - 40 to 45amps - should be fitted at the consumer unit. |
||||
An ordinary domestic oven and hob of 5-8kw will require 6mm2 twin and earth cable on runs of 15m or less. Longer cable runs and larger range-style ovens, double ovens etc may require 10mm2 cable. A suitably sized MCB - 32 to 45amps - should be fitted at the consumer unit. A switched wall plate must be fitted within 2m of the appliance. |
||||
Buried armoured cable is the usual solution to taking a spur to garages and outbuildings. Cable size is determined by loading and cable length. A 25 metre cable capable of supplying 30 amps must be at least 6mm2, buried 50 cm deep, with warning tape buried at least 15cm above it. |
||||
| Current
carrying capacity and associated voltage drop for twin and multicore armoured XLPE insulated cables |
||||||||
| Northern
and Central cables: 6941X, 6942X, 6943X, 6944X and variants |
||||||||
| Conductor |
Reference Method 1 (Clipped direct) |
Reference Method 11 (Free air) |
||||||
| Cross Sectional Area |
1 two-core cable, single phase, ac or dc. |
1 three or four core cable, three phase a.c. |
1 two-core cable, single phase a.c. or d.c. |
1 three or four core cable, three phase a.c. |
||||
| |
Current capacity |
Voltage drop |
Current capacity |
Voltage drop |
Current capacity |
Voltage drop |
Current capacity |
Voltage drop |
| mm2 |
A |
mVA-1m-1 |
A |
mVA-1m-1 |
A |
mVA-1m-1 |
A |
mVA-1m-1 |
| |
|
|
|
|
|
|
|
|
| 1.5 |
27 |
31 |
23 |
27 |
29 |
31 |
25 |
27 |
| 2.5 |
36 |
19 |
31 |
16 |
39 |
19 |
33 |
16 |
| 4 |
49 |
12 |
42 |
10 |
52 |
12 |
44 |
10 |
| 6 |
62 |
7.9 |
53 |
6.8 |
66 |
7.9 |
56 |
6.8 |
| 10 |
85 |
4.7 |
73 |
4 |
90 |
4.7 |
78 |
4 |
| 16 |
110 |
2.9 |
94 |
2.5 |
115 |
2.9 |
99 |
2.5 |
| |
|
a.c d.c |
|
|
|
a.c d.c |
|
|
| 25 |
146 |
1.90 1.85 |
124 |
1.65 |
152 |
1.90 1.85 |
131 |
1.65 |
| 35 |
180 |
1.35 1.35 |
154 |
1.15 |
188 |
1.35 1.35 |
162 |
1.15 |
| 50 |
219 |
1.00 .98 |
187 |
0.87 |
228 |
1.00 .98 |
197 |
0.87 |
| Current
carrying capacity and associated voltage drop for twin and multicore PVC insulated cables, non-armoured |
||||||||||||
| Northern
and Central cables: 6242Y, 6243Y
and variants |
||||||||||||
| Conductor |
Reference Method 3 (Enclosed) |
Reference Method 1 (Clipped Direct) |
Reference Method 11 (Free Air) |
|||||||||
| Cross Sectional Area |
1 two-core cable, with or without protective conductor, single phase,
ac or dc. |
1 three or four-core cable, with or without protective conductor, three
phase a.c. |
1 two-core cable, with or without protective conductor, single phase,
ac or dc. |
1 three or four-core cable, with or without protective conductor, three
phase a.c. |
1 two-core cable, with or without protective conductor, single phase,
ac or dc. |
1 three or four-core cable, with or without protective conductor, three
phase a.c. |
||||||
| |
Current capacity |
Voltage drop |
Current capacity |
Voltage drop |
Current capacity |
Voltage drop |
Current capacity |
Voltage drop |
Current capacity |
Voltage drop |
Current capacity |
Voltage drop |
| mm2 |
A |
mVA-1m-1 |
A |
mVA-1m-1 |
A |
mVA-1m-1 |
A |
mVA-1m-1 |
A |
mVA-1m-1 |
A |
mVA-1m-1 |
| |
|
|
|
|
|
|
|
|
|
|
|
|
| 1 |
13 |
44 |
11.5 |
38 |
15 |
44 |
13.5 |
38 |
17 |
44 |
14.5 |
38 |
| 1.5 |
16.5 |
29 |
15 |
25 |
19.5 |
29 |
17.5 |
25 |
22 |
29 |
18.5 |
25 |
| 2.5 |
23 |
18 |
20 |
15 |
27 |
18 |
24 |
15 |
30 |
18 |
25 |
15 |
| 4 |
30 |
11 |
27 |
9.5 |
36 |
11 |
32 |
9.5 |
40 |
11 |
34 |
9.5 |
| 6 |
38 |
7.3 |
34 |
6.4 |
46 |
7.3 |
41 |
6.4 |
51 |
7.3 |
43 |
6.4 |
| 10 |
52 |
4.4 |
46 |
3.8 |
63 |
4.4 |
57 |
3.8 |
70 |
4.4 |
60 |
3.8 |
| 16 |
69 |
2.8 |
62 |
2.4 |
85 |
2.8 |
76 |
2.4 |
94 |
2.8 |
80 |
2.4 |
| Current
carrying capacity and associated voltage drop for single core PVC insulated
cables, non-armoured, with or without sheath |
||||||||||||||
| Northern
and Central cables: 64911 and variants |
||||||||||||||
| Conductor |
Reference Method 3 (Enclosed) |
Reference Method 1 (Clipped Direct) |
Reference Method 11 (Free Air) |
|||||||||||
| Cross
Section |
2 cables, single phase a.c. or d.c. |
3 or 4 cables, three phase a.c. |
2 cables, single phase a.c. or d.c. |
3 or 4 cables, three phase a.c. |
Horizontal or vertical flat spaced (2 cables, single phase or 3 cables
three phases a.c.) |
Trefoil (3 cables three phase a.c.) |
||||||||
| |
Current capacity |
Voltage drop |
Current capacity |
Voltage drop |
Current capacity |
Voltage drop |
Current capacity |
Voltage drop |
Current |
Voltage drop |
Current capacity |
Voltage drop |
||
| mm2 |
A |
mVA-1m-1 |
A |
mVA-1m-1 |
A |
mVA-1m-1 |
A |
mVA-1m-1 |
A |
Single phase |
d.c. |
Three phase |
A |
mVA-1m-1 |
| |
|
|
|
|
|
|||||||||